Cathodic Protection Integrated Lightning Protection Device
Core Features
-
Graded Lightning ProtectionClass B protects against direct lightning strikes, and Class C safeguards against induced lightning, building a complete lightning protection system to discharge lightning surges at all ports.
Graded Lightning Protection -
Stray Current Isolation & DrainageStabilize voltage and drain backflow stray current to prevent overvoltage from damaging the insulation and mainboard of the potentiostat.
Stray Current Isolation & Drainage -
Intelligent Status MonitoringReal-time display of lightning strike counts, fault status and operating conditions for intuitive operation and maintenance.
Intelligent Status Monitoring
Product Features
-
High Surge Current CapacitySurge current capacity reaches 100 kA for AC terminal and 60 kA for DC terminal, far exceeding conventional 20 kA surge protectors, delivering robust protection against direct lightning strikes.
-
Safe Trip ProtectionBuilt-in failure trip device automatically isolates the unit upon damage to prevent short-circuit fire and fault escalation.
-
Integrated All-in-one DesignFull-port protection for AC, DC, reference electrode and zero potential terminals. Compact size and easy installation.
Product Technical Parameters
| No. | Project | Parameter |
|---|---|---|
| 1 | AC Input Terminal (In) | 100kA(8/20μs) |
| 2 | AC Input Terminal (Imax) | 50kA(10/350μs) |
| 3 | AC Input Terminal (Uc) | 420V |
| 4 | AC Input Terminal (Up) | ≤2.5kV |
| 5 | AC Input Terminal (In) | 60kA(8/20μs) |
| 6 | DC Output Terminal (Imax) | 100kA(8/20μs) |
| 7 | DC Output Terminal (Uc) | 130V |
| 8 | DC Output Terminal (Up) | ≤0.5kV |
| 9 | Reference & Zero-to-Cathode Terminal (In) | 60kA(8/20μs) |
| 10 | Reference & Zero-to-Cathode Terminal (Imax) | 100kA(8/20μs) |
| 11 | Reference & Zero-to-Cathode Terminal Uc) | 6V |
| 12 | Reference & Zero-to-Cathode Terminal (Up) | ≤25V |
| 13 | Rated Isolation Voltage of Zero-to-Cathode Line | -5V/+5V |
| 14 | Steady-State Drainage Current of Zero-to-Cathode Line | ≤45A |
| 15 | Fault Current (AC-rms / Power Frequency / 30 Cycles) | ≤3500A |
| 16 | Leakage Current | ≤20μA |
| 17 | Insulation Resistance | ≥10MΩ |
| 18 | Lightning Strike Counter | 999 Times |
| 19 | Operating Status Indicator Light | Steady ON when powered up |
| 20 | Fault Indicator | Lit under fault condition |
| 21 | Operating Temperature | -45℃~+60℃ |
| 22 | Altitude | ≤4000m |
Product Certification
The product has passed tests conducted by the Electrical Safety Testing Center of CNPC, Sinopec and national lightning protection testing institutions. It complies with standards GB/T 18802 and SY/T 0017, and is suitable for severe working conditions of cathodic protection stations in oil & gas and long-distance pipeline projects.
Construction Instructions
1. Installation Preparation: Inspect appearance, sealing and electrical parameters; prepare brackets, copper busbars and bolts.
2. Bracket Fixation: Install horizontally and firmly outdoors with wind and seismic resistance.
3. Equipment Fixation: Securely mount lightning protection device to prevent loosening.
4. Wiring Connection: Connect AC, DC, reference electrode and zero-potential terminals correspondingly; reliably connect copper busbars.
5. Inspection & Commissioning: Perform continuity and insulation tests; verify protection performance via simulated lightning strikes.
6.Sealing Protection: Waterproof all interfaces for outdoor rainproof and sunproof protection.